NFPA 70B — Chapter 30

#KUTitleStatus
2901 KU002901 Documentation and Records — Cables in vaults should be inspected for sharp bends, physical damage, excessive tension, oil leaks, pits, cable movemen media_required
2902 KU002902 Documentation and Records — 20.3.1 Common mode noise voltages can develop when the equipment-grounding conductor and the grounded conductor are not effecti no_media_needed
2903 KU002903 Documentation and Records — 20.3.5 An isolation transformer has separate primary and secondary windings no_media_needed
2904 KU002904 Documentation and Records — A GFCI disconnects the circuit when a current equal to or higher than the calibration point (4 mA to 6 mA) flows through media_required
2905 KU002905 Documentation and Records — 21.3.2 Ground-Fault Sensing and Relaying Equipment media_required
2906 KU002906 Documentation and Records — Covers and threaded openings should be properly tightened. no_media_needed
2907 KU002907 Documentation and Records — There are two basic types of UPS systems: static and rotary. media_required
2908 KU002908 Documentation and Records — Figure A.25.1.1(b) illustrates a typical multimodule static 3-phase UPS configuration. no_media_needed
2909 KU002909 Documentation and Records — 27.1 Information on generator sets can be found in NFPA 110 no_media_needed
2910 KU002910 Documentation and Records — 27.3.1 Ring Oiling media_required
2911 KU002911 Documentation and Records — 27.3.2.2 One reference for minimum insulation resistance media_required
2912 KU002912 Documentation and Records — recommended by the manufacturer, they should be followed. media_required
2913 KU002913 Documentation and Records — All rotating equipment should be properly aligned at operating temperature when installed. media_required
2914 KU002914 Documentation and Records — Vibration analysis equipment is useful in isolating the source of vibration that might appear to be the result of other media_required
2915 KU002915 Documentation and Records — 27.3.4 Vibration Severity Chart Velocity rms mm/sec in no_media_needed
2916 KU002916 Documentation and Records — building roof or on supports in a ground mounted array. no_media_needed
2917 KU002917 Documentation and Records — 30.3.5 Infrared thermography (IR): This noncontact electrical test can be performed on photovoltaic modules, strings, systems, media_required
2918 KU002918 Documentation and Records — 30.4.2 See NFPA 70, Article 690 no_media_needed
2919 KU002919 Documentation and Records — Lead-acid and aqueous alkaline chemistries batteries will emit hydrogen gas; if not vented, the hydrogen concentration w no_media_needed
2920 KU002920 Documentation and Records — ANSI/NETA ATS, Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems • (2) ANSI/NETA no_media_needed
2921 KU002921 Documentation and Records — A solution of water and bicarbonate of soda (baking soda) can be used to neutralize lead-acid battery spills, and a solu no_media_needed
2922 KU002922 Documentation and Records — 36.3.2 Lead-acid battery surfaces should be cleaned with a solution of water and sodium bicarbonate to avoid leak no_media_needed
2923 KU002923 Documentation and Records — Use of ohmic measurements should be in accordance with the manufacturer’s instructions and with an EMP to set baselines, media_required
2924 KU002924 Documentation and Records — 8.4.1 of NFPA 110 also requires regulated facilities to conduct a monthly EPS exercise under load to test the performance of t no_media_needed
2925 KU002925 Documentation and Records — 1.7 Receptacle Outlets no_media_needed
2926 KU002926 Documentation and Records — 1.14 Grouped Electrical Control Equipment (Such as Might Be Mounted on Walls) no_media_needed
2927 KU002927 Documentation and Records — This annex is not a part of the requirements of this NFPA document but is included for informational purposes only. media_required
2928 KU002928 Documentation and Records — Liquid level Circuit Circuit breaker with Normally Normally Disconnect breaker thermal trip open closed rh oti dp typo N no_media_needed
2929 KU002929 Documentation and Records — Figure C.1 Some Typical Electrical Symbols for Power and Control Schematics. media_required
2930 KU002930 Documentation and Records — Normally Normally Normally Normally open-timed closed-timed closed-timed open-timed Normally Normally closed open open c no_media_needed
2931 KU002931 Documentation and Records — Figure C.2 Some Typical Electrical Symbols for Electrical Control Schematic Drawings. media_required
2932 KU002932 Documentation and Records — Rectifier Rectifier diode bridge Thermistor Terminal block . no_media_needed
2933 KU002933 Documentation and Records — Figure C.3 Some Typical Miscellaneous Electrical Symbols. no_media_needed
2934 KU002934 Documentation and Records — 4.16 kV delta to 480Y/277 V wye transformer — kVA _ % impedance Neutral to grounding = electrode _— Amperes continuous _— Amp no_media_needed
2935 KU002935 Documentation and Records — Figure D.1 Typical Use of Symbols in a Single-Line Power Distribution Program. no_media_needed
2936 KU002936 Documentation and Records — Figure D.2 Wiring Diagram for a Reversing Starter with Control Transformer. no_media_needed
2937 KU002937 Documentation and Records — D.3 Figure D.3 shows a power and control schematic for a reversing starter with low-voltage remote pushbuttons. media_required
2938 KU002938 Documentation and Records — WORK ORDER REQUEST Work Order No. no_media_needed
2939 KU002939 Documentation and Records — Figure E.1 Typical Work Order Request Form. no_media_needed
2940 KU002940 Documentation and Records — AIR CIRCUIT BREAKER INSPECTION RECORD Pegs. no_media_needed
2941 KU002941 Documentation and Records — Figure E.2 Typical Air Circuit Breaker Inspection Record. no_media_needed
2942 KU002942 Documentation and Records — AIR CIRCUIT BREAKER TEST AND INSPECTION REPORT Customer Date ——_____________._ Work Order No. no_media_needed
2943 KU002943 Documentation and Records — Figure E.3 Typical Air Circuit Breaker Test and Inspection Report. no_media_needed
2944 KU002944 Documentation and Records — MEDIUM VOLTAGE VACUUM BREAKER SHEETNO. no_media_needed
2945 KU002945 Documentation and Records — Figure E.4 Typical Medium-Voltage Vacuum Breaker Form. no_media_needed
2946 KU002946 Documentation and Records — OIL CIRCUIT BREAKER TEST SHEET NO. no_media_needed
2947 KU002947 Documentation and Records — Figure E.5 Typical Oil Circuit Breaker Test Report. media_required
2948 KU002948 Documentation and Records — DISCONNECT SWITCH TEST REPORT SHEET NO. no_media_needed
2949 KU002949 Documentation and Records — Figure E.6 Typical Disconnect Switch Test Report. no_media_needed
2950 KU002950 Documentation and Records — LOW-VOLTAGE CIRCUIT BREAKER 5-YEAR TESTS FORM Pag] iii Date Substation ——_____________ Feeder ——___________________ Load no_media_needed
2951 KU002951 Documentation and Records — Figure E.7 Typical Low-Voltage Circuit Breaker 5-Year Tests Form. no_media_needed
2952 KU002952 Documentation and Records — ELECTRICAL SWITCHGEAR-ASSOCIATED EQUIPMENT INSPECTION REPORT Plan, Sate, Doeattion, Serial No. no_media_needed
2953 KU002953 Documentation and Records — Figure E.8 Typical Electrical Switchgear–Associated Equipment Inspection Record. no_media_needed
2954 KU002954 Documentation and Records — CURRENT OR POTENTIAL TRANSFORMER RATIO TEST REPORT SHEET NO. no_media_needed
2955 KU002955 Documentation and Records — Figure E.9 Typical Current or Potential Transformer Ratio Test Report. no_media_needed
2956 KU002956 Documentation and Records — OVERLOAD RELAY TEST REPORT SHEETNO. no_media_needed
2957 KU002957 Documentation and Records — Figure E.10 Typical Overload Relay Test Report. media_required
2958 KU002958 Documentation and Records — GROUND FAULT SYSTEM TEST SHEET NO. media_required
2959 KU002959 Documentation and Records — Figure E.11 Typical Ground-Fault System Test Report. no_media_needed
2960 KU002960 Documentation and Records — INSTRUMENT/METER CALIBRATION AND TEST REPORT SHEET NO. no_media_needed
2961 KU002961 Documentation and Records — Figure E.12 Typical Instrument/Meter Calibration and Test Report. no_media_needed
2962 KU002962 Documentation and Records — WATT-HOUR METER TEST SHEET SHEET NO. no_media_needed
2963 KU002963 Documentation and Records — Figure E.13 Typical Watt-Hour Meter Test Sheet. no_media_needed
2964 KU002964 Documentation and Records — PANELBOARD/CIRCUIT BREAKER TEST REPORT SHEET NO. no_media_needed
2965 KU002965 Documentation and Records — Figure E.14 Typical Panelboard/Circuit Breaker Test Report. no_media_needed
2966 KU002966 Documentation and Records — TRANSFORMER TEST AND INSPECTION REPORT SHEET NO. no_media_needed
2967 KU002967 Documentation and Records — Figure E.15 Typical Transformer Test and Inspection Report. media_required
2968 KU002968 Documentation and Records — TRANSFORMER (DRY TYPE) INSPECTION RECORD Pegs. no_media_needed
2969 KU002969 Documentation and Records — Figure E.16 Typical Transformer (Dry Type) Inspection Record. no_media_needed
2970 KU002970 Documentation and Records — TRANSFORMER (LIQUID FILLED) INSPECTION RECORD Paget. no_media_needed
2971 KU002971 Documentation and Records — Figure E.17 Transformer (Liquid Filled) Inspection Record. no_media_needed
2972 KU002972 Documentation and Records — TRANSFORMER OIL SAMPLE REPORT TOTAL NO. no_media_needed
2973 KU002973 Documentation and Records — Figure E.18 Typical Transformer Oil Sample Report. no_media_needed
2974 KU002974 Documentation and Records — 0.03 mgKOH/g MAX no_media_needed
2975 KU002975 Documentation and Records — Figure E.19 Typical Transformer Oil Trending Report. no_media_needed
2976 KU002976 Documentation and Records — TRANSFORMER INSULATION RESISTANCE RECORD Plant) — Date Scope: Power transformers of 150 kVA and greater capacity with pr no_media_needed
2977 KU002977 Documentation and Records — Figure E.20 Typical Transformer Insulation Resistance Record. media_required
2978 KU002978 Documentation and Records — VALVE-REGULATED LEAD-ACID (VRLA) STATIONARY BATTERIES AND CHARGERS INSPECTION REPORT Inspected by; — Inspection date: Us media_required
2979 KU002979 Documentation and Records — VALVE-REGULATED LEAD-ACID (VRLA) MAINTENANCE WORKSHEET BATTERY CHARGE STATUS C1OPEN CIRCUIT FLOAT 1 EQUALIZE BATTERY BUS no_media_needed
2980 KU002980 Documentation and Records — Figure E.21(b) Example of a VRLA Maintenance Worksheet. media_required
2981 KU002981 Documentation and Records — ENGINE GENERATOR INSPECTION SHEET NO. no_media_needed
2982 KU002982 Documentation and Records — Figure E.22 Typical Engine Generator Set Inspection Checklist. media_required
2983 KU002983 Documentation and Records — AUTOMATIC TRANSFER SWITCH SHEET NO.___ oF ____ CUSTOMER DATE PROVECTNO, ADDRESS AIR TEMP, REL, HUMIDITY, OWNERUSER CATE no_media_needed
2984 KU002984 Documentation and Records — Figure E.23 Typical Automatic Transfer Switch Report. media_required
2985 KU002985 Documentation and Records — UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEM INSPECTION CHECKLIST For use of this form see TM 5-694: the proponent agency i media_required
2986 KU002986 Documentation and Records — Figure E.24 Typical Uninterruptible Power Supply System Inspection Checklist. media_required
2987 KU002987 Documentation and Records — BACK-UP POWER SYSTEM INSPECTION CHECKLIST For use of this form see TM 5-694: the proponent agency is COE. media_required
2988 KU002988 Documentation and Records — Figure E.25 Typical Back-Up Power System Inspection Checklist. media_required
2989 KU002989 Documentation and Records — INSULATION RESISTANCE-DIELECTRIC ABSORPTION TEST SHEET FOR POWER CABL' Test No, —______ «Company Date ————___________ __ no_media_needed
2990 KU002990 Documentation and Records — Figure E.26 Typical Insulation Resistance–Dielectric Absorption Test Sheet for Power Cable. no_media_needed
2991 KU002991 Documentation and Records — CABLE TEST SHEET Company Date Job No. no_media_needed
2992 KU002992 Documentation and Records — Figure E.27 Typical Cable Test Sheet. no_media_needed
2993 KU002993 Documentation and Records — 1.5 Good *------------ 3to4 Questionable ------- 1 no_media_needed
2994 KU002994 Documentation and Records — Figure E.28 Typical Insulation Resistance Test Record. no_media_needed
2995 KU002995 Documentation and Records — INSULATION RESISTANCE TEST RECORD FOR ROTATING MACHINERY Reference: ANSI/IEEE 43, Recommended Practice for Scope: Testin no_media_needed
2996 KU002996 Documentation and Records — Figure E.29 Typical Insulation Resistance Test Record for Rotating Machinery. media_required
2997 KU002997 Documentation and Records — MOTOR TEST INFORMATION SHEET NO. no_media_needed
2998 KU002998 Documentation and Records — Figure E.30 Typical Motor Test Information Form. no_media_needed
2999 KU002999 Documentation and Records — GROUNDING SYSTEM RESISTANCE TEST SHEET NO. no_media_needed
3000 KU003000 Documentation and Records — Figure E.31 Typical Ground System Resistance Test Report. no_media_needed